Attic fau framing detail.
Furnaces located in an attic area shall comply with the diagram on the reverse side of this page.
Attic access may be reduced to 22 x 30 provided the largest piece of equipment can be removed through the opening.
30 inches high 762 mm 22 inches wide 559 mm 20 feet max length 6096 mm measured along the center line between the attic access opening and the attic furnace.
Chapter 7 or note special.
Wood frame house construction by l.
The framing square fig.
2 5 view a consists of a wide long member called the blade and a narrow short member called the tongue.
If the attic and roof framing is a pre.
Additionally if the attic and roof is conventionally framed ceiling joist under the location of the fau unit shall be doubled with a minimum 2x6 joists.
O where the project includes the installation of a new attic fau include the requirement of cmc 904 10 on the plans.
When a reference is made within this rule to a federal statutory provision an industry consensus standard or any other technical publication the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101 8 44 01 of the administrative code.
An attic in which a fau is installed shall be accessible by an opening and passageway 30 x 30 in size.
H provide additional combustion air in attic space where fau is located as required per c m c.
Chapter 14 framing details for plumbing heating and other utilities 97 plumbing stack vents 97 bathtub framing 98 cutting floor joists 98 alterations for heating ducts 99.
If the attic and roof framing is a prefabricated engineered truss system an engineering report wet stamped and signed by a licensed engineer shall be submitted for review and approval prior to issuance of a building permit.
Install passageway platform minimum 24 inches width and maximum 20 feet in length to fau.
If the attic and roof framing is a prefabricated engineered truss system an engineering report wet stamped and signed by a licensed engineer shall be submitted for review and approval prior to issuance of a building permit.